| Sign In | Join Free | My infospaceinc.com |
|
Model Number : APView400
Payment Terms : T/T
Communication : RS485,Modbus-RTU protocol;Ethernet
Delivery Time : 3-5 work days
Brand Name : Acrel
Supply Ability : 5000pc/day
Accuracy : Class 0.5
Place of Origin : China
MOQ : 1pc
Describe
Acrel APView400 Power Quality Analyzer is a professional power - quality monitoring device for PQM System. It complies with IEC61000 - 4 - 30 Ed3 Class A and IEC60253 - 22 Class 0.2S standards. With advanced functions like Disturbance Waveform Recording and Disturbance Direction Detection, it can record over 2000 waveforms and 5000 Sequence of Events (SOE). It also features high - precision measurement, a high - performance multi - core platform, and an embedded operating system. The device is suitable for power - supply systems up to 35kV and is widely used in industries like semiconductors, petrochemicals, steel, hospitals, data centers, and transportation. It also supports various communication protocols such as Modbus - RTU, Modbus - TCP, and IEC61850 MMS, making it a comprehensive solution for power - quality monitoring.
Specifications
| Technical Parameter | Value |
| Rated Value | AC voltage:AC/DC220V, AC/DC110V or DC48V |
| AC current:AC1A,5A; | |
| Overload capacity | 1.2In, continuous working |
| 20 times for 1 second | |
| power supply | Rated: AC/DC220, AC/DC110V or DC48V |
| Permissible deviation: -20%-+20% | |
| Power consumption:≤15W | |
| Power Consumption | ≤0.5VA (single phase) |
| Measuring rage | 0-1.2In |
| Digital output | Mechanical service life: ≥10000 |
| Output mode: Passive contacts | |
| Switching capacity: ≤4000W or ≤384VA | |
| On-state current: ≥16A(AC250V/DC24V) in the continuous mode; | |
| ≥30A for a short term (200ms) | |
| Accuracy | Class 0.5 |
| RMS Voltage:±0.1% | |
| RMS Current:±0.1% | |
| P,Q,S:±0.2% | |
| Power factor:Class 0.5 | |
| Voltage deviation:0.1% | |
| Frequency deviation:±0.001Hz | |
| Communication | RS485,Modbus-RTU protocol;Ethernet. |
| Three-phase unbalance | Voltage unbalance:±0.15% |
| Current unbalance:±1% | |
| Power frequency withstand voltage | Between power supply set of terminals and signal input, output set of terminals 2kV/1min (RMS) |
| Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV | |
| Temperature | Operation: -10℃~+55℃Storage: -30℃-+80℃ |
| Humidity | ≤95%RH, no condensation ,without corrosive gas |
| Altitude | ≤ 2500m |
Dimension & Wiring Diagram


Application Scenario

Contact

|
|